Of all the gases used to kill an electric arc, sulphur hexafluoride (SF6) is the most effective. It is heavy, chemically stable, strongly electronegative, and its dielectric strength is 2.5–3 times that of air. The modern high-voltage SF6 breaker uses a single-pressure puffer-piston design: instead of storing gas at two pressures, it squeezes the gas itself at the moment of opening and blasts it across the arc. This post explains its construction and working principle.
Construction of the puffer-type SF6 circuit breaker
The interrupter is enclosed inside a hermetically sealed porcelain or grounded metal tank filled with SF6 gas at 5–6 bar pressure. It has four main parts:
| Part | Construction |
|---|---|
| Fixed contact assembly | Stationary silver-plated copper fingers equipped with a central tungsten-copper (Cu-W) arcing rod, which takes the heat of the arc so the main contacts stay clean. |
| Moving puffer cylinder & contacts | A hollow moving contact cylinder mechanically linked to the operating rod, which slides over a stationary internal piston. |
| PTFE (Teflon) nozzle | A convergent-divergent insulating nozzle mounted at the tip of the moving cylinder, which channels the compressed SF6 gas axially across the arc column. |
| Adsorbent filters | Activated alumina filters inside the chamber, which absorb toxic arc decomposition by-products (SF4, SOF2) and moisture. |
Cross-section of the interrupter
Figure 1(b): Cross-sectional view of a single-pressure puffer-type SF6 circuit breaker interrupter. (Diagram redrawn for this post.)
Working principle
In the closed state, normal current flows through the main outer contacts while the SF6 gas inside and outside the puffer cylinder remains at uniform pressure (about 5 bar). When a fault occurs, the operating mechanism pulls the moving contact and puffer cylinder rapidly to the right, against the stationary piston. This relative motion compresses the SF6 gas trapped inside the puffer volume by an additional 3–6 bar.
As the arcing contacts separate, an arc is drawn inside the throat of the PTFE nozzle. The highly compressed SF6 gas blasts axially through the nozzle across the arc. Because SF6 is strongly electronegative, its neutral molecules rapidly capture free conduction electrons to form heavy, immobile negative ions:
SF6 + e− → SF6− and SF6 + e− → SF5− + F
Removing the free charge carriers while radially cooling the arc core collapses the arc's conductivity. At current zero, the dielectric strength (2.5–3 times that of air) recovers within microseconds, extinguishing the arc without current chopping.
Worked example: how hard does the puffer squeeze?
The chamber starts at 5–6 bar. The puffer stroke adds a further 3–6 bar of compression, so the gas blasting through the nozzle is at roughly:
5 bar + 3 bar = 8 bar to 6 bar + 6 bar = 12 bar
That is, the puffer roughly doubles the gas pressure in a few milliseconds, using only the mechanical energy of the opening stroke — no external compressor is needed. The higher the fault current, the faster the mechanism is driven, so the blast is strongest exactly when the arc is hottest.
Key points to remember
- The puffer-type SF6 breaker is a single-pressure design: gas at 5–6 bar, compressed by a further 3–6 bar during opening.
- The PTFE nozzle directs the compressed gas axially across the arc column.
- SF6 is strongly electronegative — it captures free electrons (SF6 + e− → SF6−) and cools the arc.
- Dielectric strength is 2.5–3 times that of air and recovers within microseconds at current zero.
- Adsorbent (activated alumina) filters absorb SF4, SOF2 and moisture produced by the arc.
Based on Power System Protection & Switchgear.