When a circuit breaker interrupts a fault, the voltage that appears across its contacts immediately after the arc goes out is called the restriking voltage — the transient recovery voltage. If this voltage rises faster than the contact gap can recover its dielectric strength, the arc restrikes and the breaker fails. This post derives the restriking voltage from first principles and proves that its rate of rise (RRRV) is directly proportional to the natural frequency of the circuit.
The circuit after contact separation
After the contacts separate, the faulted circuit reduces to a simple series L–C loop fed by the supply voltage: the system inductance L and the stray capacitance C across the breaker, with the resistance neglected. Two facts set the initial conditions:
- The fault current lags the supply voltage by 90°, so at the instant of arc extinction (t = 0, when the current is zero) the supply voltage is at its peak value Vm.
- At t = 0 the capacitor voltage is zero, because the arc had shorted the contacts: vc(0) = 0, and the current is zero: i(0) = 0.
Figure 3.3: Transient restriking voltage after arc extinction. The voltage rises from zero to a peak of 2Vm in half a natural cycle; its steepest slope (maximum RRRV) occurs at ωnt = Ï€/2. (Schematic, not to scale — one natural oscillation cycle shown.)
Derivation
Applying KVL to the L–C loop after separation, with the supply at its peak Vm:
L(di/dt) + vc = Vm
Since the capacitor current is i = C(dvc/dt), this becomes a second-order equation in vc:
LC(d²vc/dt²) + vc = Vm
Solving by Laplace transform with the initial conditions vc(0) = 0 and i(0) = 0, and defining the natural angular frequency ωn = 1/√(LC) and natural frequency fn = 1/(2Ï€√(LC)), the restriking voltage is:
vr(t) = vc(t) = Vm(1 − cos ωnt) = Vm(1 − cos 2Ï€fnt)
Peak value and time to peak
The cosine term is −1 when ωnt = Ï€, so the restriking voltage reaches its maximum there:
Peak vr = 2Vm at ωntp = π, so tp = π/ωn = 1/(2fn)
In words: half a natural cycle after the arc goes out, the voltage across the breaker is twice the supply peak — the capacitor has been charged to 2Vm. This is why the first half-cycle after interruption is the most dangerous moment for the breaker.
Rate of rise of restriking voltage (RRRV)
Differentiating the restriking voltage gives the rate at which it rises:
RRRV(t) = dvr/dt = Vm ωn sin(ωnt) = 2π fn Vm sin(2πfnt)
The sine term is 1 when ωnt = π/2, so the maximum rate of rise is:
RRRVmax = 2π fn Vm (at ωnt = π/2)
The average rate of rise is the peak voltage divided by the time to reach it:
Average RRRV = vr(max) / tp = 2Vm / (1/(2fn)) = 4 Vm fn
Both the maximum and the average RRRV contain fn as a direct multiplier — so RRRV ∝ fn, which is what was to be proved. A circuit with a higher natural frequency (small L or small C) produces a faster-rising restriking voltage, and is therefore harder for the breaker to handle. This is exactly why resistance switching, which lowers the effective natural frequency and damps the oscillation, is used on breakers facing steep RRRV.
Key points to remember
- After arc extinction the circuit is an L–C loop with vc(0) = 0 and i(0) = 0, while the supply sits at its peak Vm.
- Restriking voltage: vr(t) = Vm(1 − cos ωnt), with ωn = 1/√(LC) and fn = 1/(2Ï€√(LC)).
- Peak vr = 2Vm at tp = 1/(2fn) — half a natural cycle after extinction.
- Maximum RRRV = 2π fn Vm at ωnt = π/2; average RRRV = 4 Vm fn.
- Therefore RRRV ∝ fn: higher natural frequency means a steeper, more dangerous recovery voltage.
Based on Power System Protection & Switchgear, Paper II, Q3(c), Exam 11 June 2026.