High-Resistance vs Low-Resistance Arc Interruption

Author: Abloom Instruction Date: November 07, 2026

When a circuit breaker's contacts separate, an arc burns between them, and the breaker's whole job is to kill that arc. There are two fundamentally different ways to do it: raise the arc's resistance until the current dies away, or keep the resistance low and wait for a natural current zero. This post explains both methods and where each one is used.



Figure 3.1: High-resistance vs low-resistance arc interruption. (a) Arc current falls as Rarc rises. (b)

Dielectric recovery must outrun the restriking voltage (RRRV). (Schematic, not to scale — curve shapes only.)

1. High-resistance interruption (DC and low/medium AC)

The arc resistance Rarc is progressively increased over time so that the arc current decreases continuously to zero — without causing destructive overvoltages from L·di/dt. Since Rarc = ρ·l / A, resistance is increased by:

  • (i) Arc lengthening — via magnetic blowout coils, which stretch the arc;
  • (ii) Arc cooling — removing heat from the arc column;
  • (iii) Arc splitting — into series sub-arcs using metal splitter plates;
  • (iv) Constricting the arc — reducing its cross-section A.

Because a large amount of energy is dissipated inside the chute, this method is limited to DC and low/medium-capacity AC circuit breakers — for example MCBs and air circuit breakers (ACBs). It cannot handle the enormous energy of a high-voltage fault.

2. Low-resistance (current-zero) interruption (high-power AC)

This method is used exclusively in high-power AC circuit breakers. During the half-cycle conduction period the arc length and arc resistance are kept intentionally low, so minimal arc energy (∫ varc·i dt) is generated. The breaker then waits for the natural current zero — which occurs 100 times per second in a 50 Hz system — and at that instant (i = 0) the deionised medium rapidly rebuilds its dielectric strength.

Success is a race, described by two theories:

  • Slepian's Dielectric Race Theory — the dielectric strength of the gap must rebuild faster than the Rate of Rise of Restriking Voltage (RRRV). If the recovery voltage overtakes the gap strength, the arc restrikes.
  • Cassie–Mayr Energy Balance Theory — the medium must remove heat faster than the arc puts power in. If heat removal wins, the arc channel cools and dies; if not, it re-ignites.

Key points to remember

  • High-resistance method: raise Rarc = ρ·l/A by lengthening (magnetic blowout), cooling, splitting and constricting — DC and LV/MV AC only.
  • Low-resistance method: keep arc energy low, then use the natural current zero — for high-power AC breakers.
  • At current zero, dielectric recovery must outrun RRRV (Slepian) and heat removal must outrun power input (Cassie–Mayr).
  • The high-resistance method wastes energy in the chute, so it cannot scale to high-voltage faults.

Based on Power System Protection & Switchgear, Complete Examination Solution, Exam 07 May 2026, Q3(a).